Fire and safety · Design out fire and fuel hazards · safety-6

Size and protect a fire water reserve and pump

Without hydrants, firefighters rely on water you store. In the US, NFPA 1142 gives a method for the minimum water supply for rural structural firefighting, based on building volume, construction type and use.

How

  1. Use the fire water calculator in this module to get a first estimate with the NFPA 1142 method, then confirm the figure with your local fire service, which may have its own rules.
  2. US example: NFPA 1142 never allows less than 2,000 US gal (about 7,600 L) for a building with no exposure hazards, or 3,000 US gal (about 11,400 L) with one, and the local fire authority can raise these figures.
  3. Keep the fire reserve separate from drinking water, or set the house draw-off above the fire reserve level so daily use cannot drain it.
  4. Fit the outlet the local fire service uses. Ask them which coupling type and size they need, and place it beside a hard standing area their vehicle can reach.
  5. If you add your own fire pump, power it so it works when the main power is down (a petrol or diesel engine pump, or a protected battery circuit), and site it outside the defensible zone hazards.
  6. Keep a garden hose long enough to reach every side of the house, as US guidance suggests.
  7. Label the reserve and mark it on the map you give emergency services.

Safety: Cover and lock tank access hatches so children and animals cannot fall in.