Blackout continuity · Generator, workshop and machines · continuity-8Size the generator to your critical loads
A generator sized for critical loads uses far less fuel than one sized for the whole house. Use the running and surge figures from continuity-3.
How
- Add up the running watts of every critical load you will run at the same time.
- Find the single load with the highest extra starting watts (usually a pump, fridge or compressor) and add only that one surge, as Eugene Water & Electric Board's sizing method shows.
- Use the generator sizing calculator below. Example EWEB figures: refrigerator 700 W running plus 2,200 W extra starting; 1/2 HP well pump about 1,050 W running plus 2,200 W extra starting.
- If your generator charges batteries through an off-grid inverter/charger, size it to the charger input as described in power-15.
- Allow for altitude. Honda's manual for one inverter generator says output drops about 3.5 percent for each 1,000 ft (300 m) of altitude even with the high-altitude carburettor jet, and more without it. Check your own model's manual for altitude and heat derating.
- Take fuel use from the generator's own data. Generac lists consumption at half and full load for each model; its 10 kW unit is shown using about 0.97 US gal of propane per hour at half load and 1.48 at full load.
- Feed that consumption figure into the generator fuel calculator to see how much fuel each autonomy tier needs.
Do these first
Sources
- Generator sizing considerations. Eugene Water & Electric Board, accessed 2026-11
- How much fuel does my home standby generator use. Generac, accessed 2026-11
- Ten Steps of Resilient Power. US Cybersecurity and Infrastructure Security Agency (CISA), accessed 2026-11
- EG2800i generator owner's manual (high altitude operation). Honda Power Equipment (manufacturer), accessed 2026-11